| Routine ventilation |
Air temperature up to 40 °C; continuous operation |
Continuous-duty motor, balanced impeller, and adequate service factor |
Standard industrial axial fan with temperature-rated motor and corrosion-resistant coating |
Confirm the actual ambient temperature around the motor, not only the temperature inside the duct. |
| Moderate smoke extraction |
Up to 200 °C for 60 minutes |
Short-time high-temperature rating and heat-resistant electrical components |
Smoke-exhaust axial fan with protected motor bearings and high-temperature cable insulation |
Suitable for applications where smoke temperature rises for a limited period and the fan remains accessible for inspection. |
| Standard fire emergency duty |
300 °C for 60 minutes |
Certified emergency smoke-control performance and fire-resistant construction |
Dedicated smoke-exhaust fan tested for the specified temperature and duration |
Use the exact certified operating point required by the building fire strategy and applicable local regulations. |
| High-temperature fire duty |
400 °C for 120 minutes |
High-temperature motor protection, heat-resistant insulation, and structurally stable casing |
Two-speed or variable-speed smoke-control axial fan with a verified high-temperature rating |
Check that the rated airflow and pressure are maintained at the emergency temperature, not only at 20 °C. |
| Very severe smoke exposure |
600 °C for 120 minutes |
Specialized fire-rated assembly, thermal protection, and tested emergency operation |
Use only equipment with a documented test classification matching the required temperature and duration |
Do not extrapolate performance from a lower-temperature rating. The complete fan assembly and installation arrangement require verification. |
| Required airflow |
Approximately 5,000–100,000 m³/h, depending on the protected space |
Impeller diameter, blade angle, rotational speed, and system resistance must be matched |
Select from the fan curve at the actual design airflow and pressure |
Airflow demand should be calculated from the smoke-control design, compartment volume, leakage, make-up air, and required tenability conditions. |
| System pressure |
Approximately 100–1,500 Pa for many ducted smoke-exhaust systems |
Stable fan performance at the required static or total pressure |
Use a high-pressure axial configuration or guide-vane arrangement where duct resistance is significant |
Include duct friction, bends, dampers, filters, louvers, discharge fittings, and pressure losses at elevated temperature. |
| High-temperature air density |
Air density decreases as temperature increases; at 400 °C it is roughly 0.52 kg/m³ at atmospheric pressure |
Motor power and fan performance must be checked under hot-air conditions |
Review the fan curve, shaft power, and motor current at both ambient and emergency temperatures |
For a given volumetric airflow, lower hot-air density changes pressure capability, power demand, and system operating conditions. |
| Motor location |
Motor exposed to the airstream or installed outside the airstream |
Motor insulation, bearings, seals, and cooling method must suit the selected arrangement |
Prefer an out-of-air-stream motor for severe temperatures when the design permits |
External motor placement can reduce direct heat exposure, but the shaft, bearings, seals, and mounting arrangement still require temperature verification. |
| Corrosive or contaminated smoke |
Humidity, salt, dust, chlorides, combustion products, or chemical vapors present |
Suitable casing, fasteners, coating, seals, and bearing protection |
Specify galvanized or stainless construction and a coating system suitable for the exposure category |
Material selection should be based on the actual contaminants and cleaning regime; corrosion resistance does not replace fire-temperature testing. |
| Noise-sensitive installation |
Commercial buildings, transport facilities, hospitals, and occupied areas |
Low-noise blade design, vibration control, and suitable acoustic treatment |
Use a correctly sized fan at the lowest practical speed with flexible connections and vibration isolators |
Acoustic attenuators may increase system pressure loss and must be included in the fan selection calculation. |
| Control and emergency start |
Automatic start from fire alarm, smoke detector, or building management system |
Reliable starter or drive, emergency power supply, fail-safe control logic, and manual override |
Provide a dedicated smoke-control control panel with status feedback and fault indication |
Verify start-up current, emergency power capacity, interlocks, damper sequencing, and operation after loss of normal power. |
| Installation environment |
Roof, plant room, shaft, tunnel, basement, or external weather exposure |
Weather protection, drainage, access clearance, and suitable enclosure rating |
Add weather hoods, inlet or outlet guards, drainage provisions, and maintenance access as required |
Prevent rain, snow, debris, and recirculation of discharged smoke from affecting the fan or nearby air intakes. |
| Compliance and verification |
Project-specific fire and mechanical requirements |
Documented test evidence, installation instructions, and maintenance procedures |
Specify performance by temperature, duration, airflow, pressure, and installation orientation |
Confirm compliance with the applicable local code and relevant smoke-control fan test standard, such as EN 12101-3 where applicable. |